Low or 0 percent readings?

Low or 0% readings?

Are you getting constant low or 0% readings?

There are a few reasons why this might be happening but we’ll start with a quick brief on how the PTLevel works.

OPTIONAL VIDEO

To top 

HOW IT WORKS

To top 

The way that the PTLevel device works is that it measures the pressure of an air pocket created at the bottom of the liquid volume. This is done by means of our “Pressure Chamber” which is the weighted part with the black tube attached that you dropped into your tank. The supplied small diameter tube is what transports that pressure pocket to the PTLevel device where it can be measured.

Pressure chamber function

Monitoring water levels online

 

WHY THE LOW READING?

To top 

The reason why your device reads low is due to an air leak between the Pressure Chamber and the PTLevel device. The way to know that the issue is an air leak is to check your trends and see if the level reading is getting lower and lower over time.

  • Check that the connections are air tight.
  • If applicable, check that the clamps are securely in place. If you need new clamps, contact us (here) and we can provide them.
  • Check the small diameter tubing for any damage.
  • Check the threaded connection on the barb fitting at the top of the Pressure Chamber.
  • Reset the air pocket by pulling the pressure chamber out of the tank and dropping it back in after it drains.

If you’ve removed the small tubing, and will be putting it back on, we highly recommend that you place silicone or gasket sealant or high tack by Permatex to all of the barbs before pushing the tubing onto them. This ensures that any nicks or cuts to the barbs are perfectly sealed.

There is one thing to note, if you were down to really low readings and your level is actually high, your small diameter tubing may have water in it. With proper function the small tubing should not have water in it and when it does fill up, your readings will become inaccurate. The best way to fix this is to replace the small tubing, which we can provide you, or to remove it and use compressed air through it to completely dry it. If you can’t dry it completely, it can still provide poor readings.

Pressure chamber connection diagram.

    • Related Articles

    • Low or 0% Readings

      Are you getting constant low or 0% readings? There are a few reasons why this might be happening but we’ll start with a quick brief on how the PTLevel works. OPTIONAL VIDEOTo top  HOW IT WORKSTo top  The way that the PTLevel device works is that it ...
    • Level Reading Maintenance - Long Range Wireless PTLevel

      Now that you have your PTLevel setup, you’re probably wondering what to do over time in order to maintain the device and it’s readings. There’s really not much to do, but as with everything, a little bit of maintenance goes a long ways. Maintenance ...
    • Low or 0% Readings

      If you are getting low or 0% readings, you may have an air leak. Optional Video: o top How the PTLevel Works To top The way that the PTLevel works is that it measures the pressure of an air pocket created at the bottom of the liquid volume. This is ...
    • Level Reading Maintenance

      Now that you have your PTLevel setup, you’re probably wondering what to do over time in order to maintain the device and it’s readings. There’s really not much to do, but as with everything, a little bit of maintenance goes a long ways. MAINTENANCE ...
    • How do I interpret the data from my cistern liquid level monitoring system?

      Interpreting data from a cistern liquid level monitoring system involves understanding the readings provided by the system and making informed decisions based on those readings. We've created a guide to take you step-by-step through understanding the ...